GasTech Australia Blind Guard series B-GuardTM Series GHD hydrocarbon detector is a single source dual wavelength instrument. The sensing and reference elements are self-compensating for optical integrity and other signal inhibitors. The industry standard 4 -20 mA analog output provides remote alarm, fault and calibration signals.
| Model | B-Guard GHD(Hydrocarbon) |
| Measuring gas | Combustible gas (LNG, LPG, Methane & etc) |
| Measuring type | Diffusion type |
| Sensor type | Infrared type |
| Measuring range | 0-10,000 ppm & 0-100 % LEL 0-10,000 ppm & 0-5.0% Vol |
| Sensor life time | More than 5 years |
| Response time | <10 sec / 90% scale |
| Accuracy | ±3% / Full scale |
| Parameter controls | Non intrusive control with Magnet bar (calibration, maintenance, alarm setting) |
| Analog output : Measuring signal | 4-20 mA DC |
| Maintenance signal | 3 mA DC |
| Calibration signal | 2 mA DC |
| Fault signal | 0 mA DC |
| Cable / Distance | Power + signal cable: 3 wire (above CVVS 1.5sq) / 500m max. |
| Conduit pipe | 1/2" & 3/4" PF, NPT (3/4" PF standard) |
| Mounting type | 2" Pole mount, Wall mount, Duct mount |
| Operating temperature | -20℃ ~ +50℃ |
| Operating humidity | 5 ~ 99%.RH (non-condensing) |
| Operating power | 18 ~ 31V DC (24V DC normal) / 300mA max. |
| Dimensions | 301.5 x 152 x 109 (W X H X D) |
| Weight | 2.5kg |
| Approval | Flame proof structure (Ex d IIC T6),ATEX, IECEx |