GASTECH News ›› 

B-Guard Ir CO2

B Guard IR CO2 Detector

 

GasTech Australia Blind Guard series B-GuardTM Series GHD CO2 detector is a single source dual wavelength instrument. The sensing and reference elements are self-compensating for optical integrity and other signal inhibitors. The industry standard 4 -20 mA analog output provides remote alarm, fault and calibration signals.

 

 

 

 

KEY FEATURES

  •  
  • Continuous detection of CO2 gas  in explosion hazardous area with flame proof structure
  • State of art Infra red detection principle
  • Long service life (more than 5 years)
  • Low operation cost due to maintenance free
  • Operation at no oxygen environment
  • Self diagnosis function with built-in Microprocessor
  • Rapid response time (with 10 secs)
  • 4-20mA DC output signal
  • Easy configuration of monitoring system with RS-485 Modbus(isolated) Serial communication function

APPLICATIONS

  •  
  • Refineries
  • Gas turbines
  • Drilling and production platforms
  • Chemical plants
  • Fuel loading facilities
  • Compressor stations
  • Oil well logging
  • Wastewater treatment facilities
  • LNG/LPG processing and
  • storage facilities
  • Transportation facilities

SPECIFICATIONS

Model
B-Guard GHD(Hydrocarbon)
Measuring gas CO2 gas (Carbon Dioxide) 
Measuring type Diffusion type
Sensor type Infrared type
Measuring range 0-5% Vol   
0-2% Vol
Sensor life time More than 5 years
Response time <10 sec / 90% scale
Accuracy ±3% / Full scale
Parameter controls Non intrusive control with Magnet bar (calibration, maintenance, alarm setting)
Operation mode display 4-LED (Power, 2-Alarm, 1-Trouble)
Measuring value display LCD display (Built-in Back light 2-Line, 16 characters)
Alarm signal output 250V 1A / 3-SPST Relay contact (2-Alarm, 1-Trouble)
Output signal  
Analog output : Measuring signal 4-20 mA DC
Maintenance signal
3 mA DC
Calibration signal 2 mA DC

 
Fault signal 0 mA DC
Digital output RS-485 MODBUS (Option)
Cable / Distance Power + signal cable: 3 wire (above CVVS 1.5sq) / 500m max.
RS-485 data communication cable
1par (UL2919 RS-485) / 1,000m max.
Conduit pipe 1/2" & 3/4" PF, NPT (3/4" PF standard)
Mounting type
2" Pole mount, Wall mount, Duct mount
Operating temperature -20℃ ~ +50℃
Operating humidity 5 ~ 99%.RH (non-condensing)
Operating power 18 ~ 31V DC (24V DC normal) / 300mA max.
Dimensions 301.5 x 152 x 109 (W X H X D)
Weight 2.5kg
Approval Flame proof structure (Ex d IIC T6),ATEX, IECEx

 

ORDERING INFORMATION

  • 67-9092 -CO2 : B-Guard IR Smart Transmitter, 4-20mA, 0-5% VOL IECex

DOWNLOADS