GTA Millenium Series Infrared hydrocarbon detector is a single source dual wavelength instrument. The sensing and reference elements are self-compensating for optical integrity and other signal inhibitors. The industry standard 4-20mA analog output provides remote alarm, fault and calibration signals.
The GTA Millenium Series hydrocarbon detectors are designed to be used in the same applications where catalytic bead sensors have been applied.
| Operating Voltage | 24VDC (18 – 32VDC) |
| Current Draw | 210mA avg, 400mA peak |
| Power Consumption | 5 W Max. |
| Analog Output | 4 – 20 mA (sourced) |
| Range | 0 – 100% LEL |
| Gases | Methane, Propane, and Butane. Other hydrocarbon gases are available |
| Accuracy | ± 3% 0 to 50% LFL ± 5% 51 to 100% LFL |
| Response Time | T50 < 5 seconds T90 < 10 seconds |
| Temperature Rating | - 40C° to + 70°C - 40F° to + 158°F |
| Humidity | 0-99% (non-condensing) |
| Housing Construction | Nickel-plated aluminum and stainless steel. Optional stainless steel model. |
| Approvals | CSA, FM Performance Approved |
| Classification | Class 1, Div. 1, Groups B, C & D |
| Mounting | 3/4" NPT |
| Weight | 2 lbs. (0.9 kg.) |
| Current Output | Status |
| 4-20 mA | Normal measuring |
| 0.0 mA | Unit Fault |
| 0.2 mA | Reference channel fault |
| 0.4 mA | Analytical channel fault |
| 0.8 mA | Unit Warm up |
| 1.0 mA | Optics fault |
| 1.2 mA | Zero drift fault |
| 1.6 mA | Calibration fault |
| 2.0 mA | Unit Spanning |
| 2.2 mA | Unit Zeroing |
| 4.0 mA | Zero gas level |
| 5.6 mA | 10% LEL |
| 8.0 mA | 25% LEL |
| 12 mA | 50% LEL |
| 16 mA | 75% LEL |
| 20 mA | 100% LEL |
| 20.1-23 mA | Over range (> 100 %) |